4/3C Type MP-GC With Ground 2BC + 1GC EPR Mining Industrial Cable 15000V
Where are we? 4 Continents 8 Countries
Got any Questions?
Speak with a real person who will go out of their way to help you!
Call Us: 1-516-482-6313Text Us: 1-516-703-3460
Chat
Live Chat: Bottom Right Corner!
Email Us
info@nassaunationalcable.com
Quick Support
Product Information
Specification
4/3C Type MP-GC With Ground 2BC + 1GC EPR Mining Industrial Cable 15000V
Applications:
• Mine Power Feeder Cable Extra Heavy Duty EPR/CPE 90°C MSHA Mining grade
• TYPE MP-GC -15000 VOLTS -100% INSULATION LEVEL
• For use as trailing mining cables. For use from 5 kV up to 25kV when installed
inducts, conduit, open air and direct burial in wet and dry locations. Other industrial,
mining applications
Also Known As:
4/3C Type MP-GC EPR Power Cable, 4/3C Type MP-GC EPR Cable, 4/3C MP-GC Type Mining Power Feeder Cable, 4/3C American Mustang Type MP-GC Cable, 4/3C Type MP-GC, 4/3C Type MP-GC EPR , 4/3C Type MP-GC 15000V
Conductors: Bare copper concentric strand in accordance with ASTM B 8
Conductor shield: Semi-conductive tape and layer over the conductor. ICEA S-75-381 sec. 3.14
Insulation: Ethylene-propylene rubber (EPR). ICEA S-75-381
Insulation shield: Semi-conducting compound as per 4.5 of ICEA S-75-381 and 0.005” copper tape
Circuit identification: Color thread: black, red white applied under metallic shielding tape. ICEA S-75-381 sec.4.6
Grounding: Annealed tin coated copper Class B comply with Tab. 4-1 of ICEA S-75-381
Ground check: Bare copper conductor. ICEA S-75-381 Tab. 4-1.Insulation color: yellow
Assembly: Three power, the ground check, two tinned copper grounding conductors cabled with cured rubber fillers as required to make an essentially round core
Separator: A single faced rubber filled binder tape applied over core.
Outer jacket: A CPE thermosetting compound, extra heavy duty as per Table 3-3,sec. 3.21
Features: Ozone, sun, weather and flame resistant. Oil and heat resistant. Maximum continuous conductor temperature 90°C. Indent printed for easy identification.
Standards: ICEA S-75-381/NEMA WC-58,ASTM B-8
Specification:
• Part No: MPGC15KV4-3-CPE
• Power Conductor Size: 4 AWG
• Power Conductor Stranding: 7
• Ground Size: 8 AWG
• Ground Check Size: 8 AWG
• Nominal Insulation Thickness: 0.175 Inches
• Nominal Jacket Thickness: 0.140 Inches
• Nominal O.D: 1.84 Inches
• Approx. Weight: 2140/1000 lbs
• Maximum Permissible Tensile Force (N): 950
• PowerGrounding Conductor Size: 4 AWG
• Power Conductor Resistance at 25°C (Ω/1000Ft): 0.258
• Grounding Conductor Resistance at 25°C (Ω/1000Ft): 0.129
• Ground-check Conductor Resistance at 25°C (Ω/1000Ft): 0.652
• Inductance per unit length (mH/1000Ft): 0.129
• Operating Capacitance per unit length (µF/1000Ft): 0.07
• Permissible short-circuit Current (1s) (2): 3.03 kA
• Ampacity(1) 40°C Ambient Temp: 122 A
*Data provided on this page is subject to change based on different manufacturers' variances